Don’t size a solar system by your roof. Size it by your night. The roof tells you how many panels fit. The night tells you what you actually need, and those are two very different numbers.
Most quotes run forwards. They start with the panels, add a battery that looks about right, and pick an inverter last. The trouble shows up at half past seven on a winter evening, when the grid is down, the kettle goes on, and the inverter trips. The sums below run the other way: night first, peak next, sun last.
Watch it run
Press play, or pick a step (1 to 5). The tour takes about 80 seconds.
The narrated walkthrough
The full version, about two and a half minutes, narrated with a synthetic voice.
The home we are sizing
This is an illustrative household. The appliance figures are invented for the example, not measured, and not from a client. It uses gas for the stove and has an electric geyser (hot-water cylinder). Every appliance is watts multiplied by hours of use:
| Appliance | Power | Hours a day | Energy a day |
|---|---|---|---|
| Lights, 10 LED bulbs | 80 W | 5 | 0.40 kWh |
| Fridge-freezer, average | 100 W | 24 | 2.40 kWh |
| TV and decoder | 120 W | 5 | 0.60 kWh |
| Router and fibre box | 20 W | 24 | 0.48 kWh |
| Two laptops | 120 W | 4 | 0.48 kWh |
| Kettle | 2,000 W | 0.3 | 0.60 kWh |
| Microwave | 1,200 W | 0.2 | 0.24 kWh |
| Washing machine | 500 W | 1 | 0.50 kWh |
| Total without the geyser | 5.70 kWh | ||
| Electric geyser | 3,000 W | 2.5 | 7.50 kWh |
Look at the last row. The geyser alone is larger than everything else in the house put together. A solar system that tries to carry it on battery needs a far bigger battery and a far bigger array, so we leave it out and come back to it at the end. With it, this home would use 13.2 kWh a day, about 400 kWh a month, which sits at the lower end of the 400 to 500 kWh a month that one South African energy retailer quotes for smaller homes.
Step 1: the night sets the battery
Ask one question: how long can I bear the dark, and what must keep running? Here the answer is four hours of grid failure in the evening, with only the essentials on: lights, fridge, TV, router and laptops. The four-hour window is a design choice. Pick your own from your own experience of outages.
| Essential load | Power |
|---|---|
| Lights | 80 W |
| Fridge | 100 W |
| TV | 120 W |
| Router | 20 W |
| Laptops | 120 W |
| Total | 440 W |
440 W for 4 hours is 1.76 kWh. Add one boil of the kettle (2,000 W for 6 minutes, 0.1 hours) and it is 1.96 kWh. That is what the battery must deliver.
A battery’s label is not what you can use. Two losses sit between the label and your lights:
- Usable capacity. Home lithium iron phosphate batteries are rated to be discharged to a set depth, often about 90%. A 5.12 kWh unit with a 90% rating, for example, is listed by Deye.
- Round-trip efficiency. Not every kWh that goes in comes back out. Victron’s datasheet gives 92% for lithium iron phosphate.
So the label must be at least 1.96 ÷ (0.90 × 0.92) = 1.96 ÷ 0.828 = 2.37 kWh. The next common size is 5 kWh, and that leaves room for a longer outage or a second boil. Your own battery’s datasheet is the authority on both percentages.
Step 2: the peak sets the inverter
Now the inverter. Don’t ask how much energy the house uses. Ask what the busiest minute looks like. An inverter is rated in watts, not kilowatt-hours, so the daily total tells you nothing about it.
The kettle is 2,000 W. Add the 440 W of essentials running at the same moment and the peak is 2,440 W. Do not run an inverter flat out. Keeping it at 80% of its rating or less, the inverter must be at least 2,440 ÷ 0.8 = 3,050 W, and you buy the next rating above that. Ratings differ by maker.
One kettle decides the inverter. Take the kettle off the inverter, on gas or on its own grid-only circuit, and the same sum gives 440 ÷ 0.8 = 550 W. That single appliance moves the requirement by a factor of more than five.
This is the same logic that sizes a generator in a plant: the largest transient, not the largest continuous load, drives the choice. Two checks the animation leaves out belong here too. Motors in fridges, pumps and washing machines draw several times their running watts for a moment when they start, so read the inverter’s surge rating on its datasheet. And any appliance you add later changes the peak.
Step 3: the sun sets the panels
Only now do the panels get a say. The roof must supply the 5.70 kWh the home uses in a day. Two numbers turn that into a panel size:
- Peak sun hours. One kilowatt of panels in full sun for one hour makes one kilowatt-hour. A commercial solar-resource table gives about 5.3 to 5.5 peak sun hours a day for Gauteng. We use the low end, 5.3.
- System efficiency. Heat, wiring, inverter losses and dust mean you never get the full figure. We keep 75%, a round design allowance for this example, not a measured value.
One kilowatt of panels therefore delivers 5.3 × 0.75 = 3.975 kWh a day. The home needs 5.70, so it needs 5.70 ÷ 3.975 = 1.43 kWp of panels. Panels come in whole units. Three 550 W panels give 1.65 kWp and, on an average day, 1.65 × 3.975 = 6.56 kWh, which covers the need with room to spare.
A cross-check against measurement: 3.975 kWh a day is about 1,451 kWh per kWp a year. A peer-reviewed study of nine South African sites modelled specific yields from about 1,437 to 1,819 kWh per kWp a year. The 1,451 sits at the cautious end of that range, which is the right end to design from.
Now the geyser. Adding its 7.5 kWh a day grows the array by 7.5 ÷ 3.975 = 1.89 kWp, more than doubling it. Heating the water directly with the sun, or with a heat pump, is usually the better way to deal with it than a bigger battery and a bigger array.
The answer, in the right order
| Step | Question | Answer for this home |
|---|---|---|
| 1. Night | What must run, for how long? | Battery of at least 2.37 kWh, so a 5 kWh unit |
| 2. Peak | What is the busiest minute? | Inverter of at least 3,050 W (2,440 W at 80% load) |
| 3. Sun | What must the roof make in a day? | 1.43 kWp needed, so 3 × 550 W = 1.65 kWp |
The roof comes last.
What this animation leaves out
It is a teaching example, not a design, and a real home needs more than the arithmetic above.
- Winter and weather. The 5.3 hours is a Gauteng figure from one commercial table, and the table itself notes a range for the Western Cape of 4.7 to 6.0. Winter days are shorter and cloudier. Design from the worst month you must cover, not the average.
- Orientation, tilt and shade. All of them cut the 75%.
- Battery ageing. A battery holds less every year. Leave margin.
- Outage length. Four hours is an assumption. Your own outage history is the better input.
- Protection and cabling. Breakers, isolators, surge protection and cable sizing are separate design work.
- Rules. Many municipalities require small-scale embedded generation to be registered, and installers issue a certificate of compliance. Requirements differ by municipality, and the standards position has been in flux, so check with yours. The City of Cape Town’s page is one example of what a municipality asks for. A registered electrician should design, install and certify the real system.
The question to ask any installer
Every figure above comes from a question asked in a particular order. A quote that starts with a panel count and never asks what has to keep running when the grid is down has skipped the first two steps.
If an installer quoted you panels first and the battery second, what would you ask them about your night?