IEC 60534 liquid sizing at three flow cases. Change any number and watch Cv, percent open and the choked-flow limit respond.
1 · Operating cases
Minimum
Normal
Maximum
Flow Q (m³/h)
Valve ΔP (bar)
Kv required
Cv required
Percent open
Control range
Choked flow
Kv = Q / (N1 · √(ΔP / ρr)) with N1 = 1 (Q in m³/h, ΔP in bar), and Cv = Kv / 0.865. Fp = 1: the valve is assumed the same size as the pipe, with no reducers.
2 · Valve and fluid
3 · Where each case sits on the trim
Choked limit: …
Equal-percentage trim: Cv = Cvr · R(x − 1), where x is the fraction open. The shaded band is the usual 20–90% control range. Valve ΔP falls as flow rises because the pump head drops and line losses grow, which is why an equal-percentage trim suits a valve that takes only part of the system pressure drop.
Educational model for understanding, not for final selection. The manufacturer's Cv, FL and rangeability data govern real sizing, and real trims depart from the ideal curve near closed. The worked example follows a process engineer's public LinkedIn post; the model is independently rebuilt and its numbers checked against a second calculation.