Here is how to build a very safe system that shuts your plant down all the time.
Put two sensors on every measurement, and trip when either one says so. Either sensor can save the day, so the system is hard to fool. It is also easy to trip: every false alarm from either sensor stops the plant.
Now run that backwards. It is the oldest trade in functional safety. Protection against a missed demand costs you protection against a false trip, and the voting arrangement sets the exchange rate.
This is part of a series that takes the worked example from How a SIL calculation works apart, one assumption at a time. The numbers are illustrative, not from a client. The device we vote on is the pressure transmitter, PT-101.
The narrated walkthrough, about two minutes, with a synthetic voice.
What 1oo2 and 2oo3 mean
“MooN” reads as M out of N. It is the number of devices that must call for a trip before the trip happens.
- 1oo1: one sensor.
- 1oo2: either of two sensors trips the function.
- 2oo2: both sensors must agree.
- 2oo3: any two of three sensors must agree.
Two scoreboards
To isolate the voting effect, we count only the transmitter’s silent dangerous failures (2.1×10⁻⁷ per hour), tested every 12 months. For false trips we use its safe failure rate, assumed at 3.0×10⁻⁶ per hour. That safe rate is a new illustrative figure, added for this article. We assume no common cause between the sensors, which the next article takes away.
| Voting | Chance of failing on demand | False trips per year |
|---|---|---|
| 1oo1 | 0.00092 | 0.0263 (about once in 38 years) |
| 1oo2 | 1.1×10⁻⁶ | 0.0526 (about once in 19 years) |
| 2oo2 | 0.0018 | 3.8×10⁻⁶ |
| 2oo3 | 3.4×10⁻⁶ | 1.1×10⁻⁵ |
The simplified formulas behind the first column are λDU×TI÷2 for 1oo1, (λDU×TI)²÷3 for 1oo2, λDU×TI for 2oo2 and (λDU×TI)² for 2oo3.
Read it across. 1oo2 is far safer than one sensor, and it doubles your false trips. 2oo2 is the mirror image: almost no false trips, and twice as likely to miss a real demand as a single sensor. 2oo3 keeps nearly all of the 1oo2 safety and almost none of its false trips. The price is a third sensor.
The catch: it only fixes the part you voted
The whole function was PFDavg = 0.0050274, and the transmitter contributes 18.9% of it. Replace PT-101 with a 1oo2 pair and the function reaches 0.0041087. Use 2oo3 and it reaches 0.0041110. That is about an 18% improvement, and no sensor arrangement can give more: even a perfect sensor removes only its own 18.9%.
The valve still carries 53.9%. Voting on the cheapest, easiest part to duplicate does not fix the part that matters most. (For these loop totals, the sensor’s small detected-failure term is kept at its single-sensor value, a conservative simplification.)
What this simple model leaves out
- It assumes the sensors fail independently. Real ones share impulse lines, power, software and calibration, which is the subject of the next article.
- It counts only the silent dangerous failures, and uses simplified standard formulas for a low-demand function. It is for understanding, not for certifying a design.
Where on your plant does the redundancy sit: on the part that fails most, or on the part that is easiest to duplicate?