Don’t ask how safe a plant is. Ask how it fails. That one change of question is the whole idea behind a SIL calculation.

What SIF and SIL mean

A safety instrumented function (SIF) is an automatic guardian: a sensor that measures a process, a logic solver that decides whether to act, and a final element, usually a valve, that moves the process to a safe state.

A safety integrity level (SIL) rates how reliably that guardian does its job when it is needed. IEC 61511 defines four levels. For a function that is called on rarely (low-demand mode, no more than about once a year), each level is a band of the average probability of failure on demand (PFDavg):

Level PFDavg band
SIL 1 1×10⁻² to 1×10⁻¹
SIL 2 1×10⁻³ to 1×10⁻²
SIL 3 1×10⁻⁴ to 1×10⁻³
SIL 4 1×10⁻⁵ to 1×10⁻⁴

A smaller number is a more reliable guardian. SIL measures failure, not success.

The worked example

The numbers below are illustrative. They are not from a real plant or a client.

SIF-101 protects a vessel from high pressure: a pressure transmitter (PT-101), a logic solver and a shutdown valve (ESDV-101). A hazard study (HAZOP) found the danger, and a layer-of-protection analysis (LOPA) set the target at SIL 2. The inputs:

  • Low-demand mode, proof test once a year (TI = 8,760 hours), mean time to repair 24 hours.
  • Each part has two failure rates per hour: λDU, dangerous and undetected (only a proof test finds it), and λDD, dangerous but detected by diagnostics.
Part λDU λDD
PT-101, sensor 2.1e-07 1.2e-06
Logic solver 3.0e-07 2.3e-06
ESDV-101, valve 6.0e-07 3.4e-06

The calculation

A hidden fault, on average, sits unnoticed for half the test interval: 8,760 / 2 = 4,380 hours. For each part:

PFD = (λDU × TI/2) + (λDD × MTTR)

Part λDU × 4,380 + λDD × 24 = PFD
PT-101 9.198e-04 2.88e-05 9.486e-04
Logic solver 1.314e-03 5.52e-05 1.3692e-03
ESDV-101 2.628e-03 8.16e-05 2.7096e-03

The loop fails if any link fails, and the chances are small, so they add: PFDavg = 0.0050274, about 5.03×10⁻³. That sits inside the SIL 2 band (1×10⁻³ to 1×10⁻²). Put plainly, if this function were needed 1,000 times it would fail to act about 5 times.

The valve alone contributes 53.9% of that total, the logic solver 27.2% and the sensor 18.9%. If the number ever had to come down, the valve is where to look first.

The mistake to avoid

A tempting shortcut is λDU / (λDU + λDD). It has no time in it, so it is a ratio, the fraction of dangerous faults that go undetected. It is not a probability, and it does not tell you how often the function fails on demand.

What this does not cover

A PFDavg inside a band is necessary, not sufficient. IEC 61511 also sets architectural constraints (hardware fault tolerance and safe failure fraction), and redundant layouts need a common-cause allowance. This example uses the simplified single-channel formula to show the idea, not to certify a design.

The full walkthrough

The full version, just under two minutes: the target, the inputs, the clock, each device, the sum and the verdict.

Keep going: the rest of the series

This article is the first of a series that takes the same example apart, one assumption at a time.

  1. How a SIL calculation works (this article)
  2. What happens when a proof test is skipped
  3. Diagnostic coverage: what your diagnostics really catch
  4. 1oo2 vs 2oo3 voting
  5. Common cause failure and the beta factor
  6. Hardware fault tolerance and safe failure fraction
  7. How to set a SIL target with LOPA
  8. Proof test coverage
  9. PFD over time and partial stroke testing
  10. Low demand, high demand and PFH
  11. Spurious trips and what they cost
  12. Bypasses and management of change
  13. A certified device is not a certified loop
  14. The valve: final element and closing time

Don’t hope it works. Prove how it fails.