The SIL number that hides the worst day: PFD over time and partial stroke testing

24 November 20263 min read

Here is how to be told your safety function is fine, on the one day it is not.

Quote the average. The average over the whole test cycle sounds reassuring, and it is true. It is also a number that no single day actually has.

Now run that backwards. The PFDavg in How a SIL calculation works is the average of a line that climbs for a year and then drops to the start again. The danger lives at the top of the climb.

This is part of that series. The data is illustrative, not from a client.

The narrated walkthrough, about two minutes, with a synthetic voice.

The sawtooth

Right after a proof test, every silent failure has just been found and fixed. The chance that the function fails on demand is almost zero. Then hidden failures accumulate. For a silent failure rate λDU, the chance grows in a straight line with time t:

PFD(t) = λDU × t, plus the small, constant detected-failure part.

Add the three devices’ silent rates, 1.11×10⁻⁶ per hour, and at the end of the 12-month cycle (8,760 hours) the peak is 0.0098892. The average over the cycle is 0.0050274. The worst day is 1.97 times the average, and only a whisker under the SIL 2 limit of 0.01.

Something worth noticing: the peak of a 12-month cycle is exactly the average of a 24-month cycle, because both equal λDU × 8,760 plus the detected part. That is why one skipped test takes the function to 0.0098892.

Why the average is still the right number

Demands arrive at random, so on average they meet the function at an average moment, and the average is what the SIL band measures. It is the honest summary for a long run. It says nothing about the single demand that arrives the day before the test, which meets a function twice as likely to fail.

Testing more often, without stopping the plant

The most expensive silent failure belongs to the valve. A partial stroke test (PST) moves the valve a short way, enough to find some failures without stopping the process, and can run far more often than a full test. Say a PST every three months (2,190 hours) finds a share c of the valve’s silent failures, and the full test finds the rest:

valve silent PFD = λDU × [c × 2,190 ÷ 2 + (1 − c) × 8,760 ÷ 2]

Partial stroke test finds Valve silent part Function PFDavg
Nothing (as worked) 0.002628 0.0050
30% of its silent failures 0.0020367 0.0044
60% 0.0014454 0.0038
90% 0.0008541 0.0033

Even a modest 30% takes the function from 0.0050 to 0.0044, and 60% takes it to 0.0038 without touching a wire.

The honest catch

Every number in that table depends on the coverage c, and the previous article showed what happens when a test’s coverage is a hope. The PST claim has to be backed by the valve’s failure modes, not by the schedule.

What this simple model leaves out

It assumes failures grow at a constant rate, that the valve is the only device with partial testing, and that tests are perfect at what they cover. The data is illustrative. This is for understanding, not for certifying a design.

On the worst day of your test cycle, is the safety function still doing the job you signed off on?