Here is how to buy two sensors and get the safety of one and a half.
Buy both from the same maker. Fit them on the same impulse line. Power them from the same supply, calibrate them on the same afternoon with the same instrument, and wire them through the same junction box. They are now two devices that fail for the same reasons at the same moment.
Now run that backwards. What remains is the beta factor: the share of failures that hit every channel at once.
This continues the series that starts with How a SIL calculation works, and picks up where 1oo2 vs 2oo3 voting left off. That article assumed the sensors fail independently. Here we take that assumption away. The data is illustrative, not from a client.
The narrated walkthrough, about two minutes, with a synthetic voice.
What the beta factor is
Common cause failure is one cause that fails more than one channel together: a shared impulse line that freezes, a power dip, a software bug in both, one wrong calibration. The beta factor (β) is the fraction of a channel’s dangerous undetected failures that behave this way.
The simplified formula for a 1oo2 pair adds a term that does not fall with redundancy:
PFD = ((1 − β) × λDU × TI)² ÷ 3 + β × λDU × TI ÷ 2
The first term is the two channels failing independently. The second is a common cause taking out both. For our transmitter, a single sensor on its own has PFD = 0.00092.
What redundancy is worth
| Beta factor | 1oo2 pair, chance of failing on demand | Safer than one sensor by |
|---|---|---|
| 0% (ideal) | 1.1×10⁻⁶ | 815 times |
| 2% | 1.9×10⁻⁵ | 47 times |
| 5% | 4.7×10⁻⁵ | 19.6 times |
| 10% | 9.3×10⁻⁵ | 9.9 times |
| 20% | 1.8×10⁻⁴ | 5.0 times |
Look at the top row, then the second. Admitting that just 2% of failures are shared cuts the benefit from 815 times to 47 times. The second term dominates quickly, and the ceiling on the gain is roughly 1 ÷ β. At 5% that ceiling is 20 times, and the table reaches 19.6.
A 2oo3 arrangement suffers the same way: at 5% common cause it gives 4.9×10⁻⁵, almost the same as the 1oo2 pair, because the shared term is the same.
How to lower the beta factor
You cannot buy it away with more of the same. You lower it by making the channels less alike and less connected:
- Separate the impulse lines, power supplies and cable routes.
- Diversify the technology, for example two different measuring principles or two different makers.
- Stagger the maintenance and calibration, so one mistake cannot reach both channels.
- Protect against the shared environment: heat, vibration, contamination.
IEC 61508 offers a scoring method for estimating β from checklists like these. Values from a few percent up to 10% or more are commonly assumed, and any value should be defended with evidence about the actual installation.
What this simple model leaves out
It uses the simplified formulas with silent dangerous failures only, one β for the whole subsystem, and illustrative data. It is for understanding, not for certifying a design.
If both of your sensors share one impulse line, how many sensors do you really have?