Why your proof test does not find everything: proof test coverage and the SIL you really have

24 November 20263 min read

Here is how to pass every proof test for 15 years and still own a broken safety function.

Test the valve every year, the way you always have. Move it, watch the light change, sign the sheet. Never test the failures that need the valve to close under real conditions. Every test passes, and a slice of the hidden failures is never looked at again.

Now run that backwards. The calculation in How a SIL calculation works quietly assumed that every proof test finds every hidden failure. Real tests find most, not all.

This is part of that series, and it builds on the skipped proof test. The data is illustrative, not from a client.

The narrated walkthrough, about two minutes, with a synthetic voice.

Proof test coverage

Proof test coverage (PTC) is the share of dangerous undetected failures that a proof test actually reveals. The rest survive the test and stay hidden, to be found only at an overhaul or when the device is replaced. In a simple model, assume that happens at the end of a 15-year life, 131,400 hours:

PFD (silent part) = λDU × [PTC × TI ÷ 2 + (1 − PTC) × lifetime ÷ 2]

The first part is the failures the test catches, exposed for half a test interval. The second is the failures it misses, exposed for half the whole life.

What a gap in coverage costs

The valve carries the largest silent failure rate (6.0×10⁻⁷ per hour). With perfect coverage its silent contribution is 0.002628. Drop the valve’s coverage to 90% and that contribution becomes 0.0063072, 2.4 times larger.

Coverage of the proof tests Function PFDavg Result
100% everywhere, as originally worked 0.0050 SIL 2
Valve at 90%, others perfect 0.0087 SIL 2, but 87% of the limit used
Valve at 80%, others perfect 0.0124 SIL 1
All three devices at 90% 0.0118 SIL 1

Look at the last row. A 90% test sounds like a good test. Applied to every device, it turns a function with comfortable margin into SIL 1. The missed 10% sits in the calculation for years while the tested 90% resets every year.

Why a valve is the usual culprit

A proof test is only as good as what it exercises. A valve that is stroked but never checked for tight shut-off, a pressure transmitter checked at one point instead of across its range, a test done with no flow and no differential pressure: each one verifies something, and misses something else. Which of the missed failures matter is a question about how the device fails, not about the test sheet.

How to raise coverage

Compare each test step with the device’s list of dangerous failure modes and mark which ones the step can reveal. Anything not covered is either a gap to close with a better test, or a failure rate that must be moved into the silent group for the whole lifetime. A coverage number with no list behind it is a guess.

What this simple model leaves out

Real tests are not all-or-nothing, and failures can be found at inspections between tests. The lifetime-based model is one common simplification, and the data is illustrative. This is for understanding, not for certifying a design.

What fraction of the valve’s dangerous failures does your proof test genuinely reveal, and who wrote that number down?