Same plant, two SILs: low demand, high demand and PFH explained

24 November 20263 min read

Here is how to get two different SIL answers from one plant, without changing a single device.

Change how often the function is called on.

Now run that backwards. A SIL is not a property of the hardware alone. It is the hardware measured against a scale, and the scale depends on how often the world asks the function to act.

This is part of the series that starts with How a SIL calculation works. Every number so far has been for a low-demand function. The data is illustrative, not from a client.

The narrated walkthrough, about two minutes, with a synthetic voice.

The three demand modes

IEC 61508 defines them by how often the function must act:

  • Low demand: called on no more than about once a year. The measure is the average probability of failure on demand, PFDavg.
  • High demand: called on more than once a year. The measure is the average frequency of dangerous failure per hour, PFH.
  • Continuous: the function is part of normal operation, always in play. PFH again.

Why two measures? When demands are rare, the proof test has time to find hidden failures between demands, so what matters is the chance the function is broken at that moment. When demands are frequent, a hidden failure does not have time to be caught, so what matters is how fast dangerous failures happen.

Two scales

SIL Low demand: PFDavg High or continuous: PFH, per hour
1 10⁻² to below 10⁻¹ 10⁻⁶ to below 10⁻⁵
2 10⁻³ to below 10⁻² 10⁻⁷ to below 10⁻⁶
3 10⁻⁴ to below 10⁻³ 10⁻⁸ to below 10⁻⁷
4 10⁻⁵ to below 10⁻⁴ 10⁻⁹ to below 10⁻⁸

The same function on both scales

Take SIF-101 exactly as worked. As a low-demand function its PFDavg is 0.0050274, which is SIL 2.

As a high-demand function, the simplest estimate of PFH is the sum of the dangerous undetected failure rates: 2.1×10⁻⁷ + 3.0×10⁻⁷ + 6.0×10⁻⁷ = 1.11×10⁻⁶ per hour. That sits just above 10⁻⁶, so it is SIL 1. Over a year that is 0.0097 dangerous failures, close to one in a hundred.

To reach SIL 2 on the high-demand scale the failure rate would need to fall by 9.9%, from 1.11×10⁻⁶ to below 10⁻⁶. Same devices, same wiring, one band apart.

Which mode is it?

The demand rate comes from the hazard study, not from a preference. In the layer of protection example, the pressure loop fails 0.1 times a year and the operator catches 90% of those, so the safety function is called on about 0.01 times a year. That is low demand by a wide margin. If the same function were called on monthly, the PFDavg scale would no longer apply.

What this simple model leaves out

The PFH estimate here is the simplest one for a single channel. Real high-demand calculations also account for diagnostics, reaction times and architecture, and the data is illustrative. This is for understanding, not for certifying a design.

How often is your safety function really called on, and where is that figure written down?