Articles / Safety

How 44 hours of bypass turns SIL 2 into SIL 1: bypasses and management of change

24 November 20263 min read

Here is how to lose a SIL 2 in under two days a year.

Bypass the function for maintenance. Just for a day. Then again for a day, later in the year, and for a few hours more when it trips on a nuisance alarm. Each bypass is reasonable, and each is logged somewhere. Nobody adds them up.

Now run that backwards. While a function is bypassed it does nothing. Its chance of failing on demand during that time is 1, not 0.005.

This is part of the series that starts with How a SIL calculation works, and it follows the cost of spurious trips, which ended on the temptation to bypass. The data is illustrative, not from a client.

The narrated walkthrough, about two minutes, with a synthetic voice.

Pricing a bypass

The average over a year is a weighted mix: the healthy time at the function’s normal PFDavg, and the bypassed time at 1:

PFDavg(year) = (1 − h ÷ 8,760) × 0.0050274 + (h ÷ 8,760) × 1

For 72 hours of bypass in the year, the average is 0.013205. That is SIL 1. The function never changed and nothing broke. Three days of being switched off was enough.

How many hours can the function afford? Set the yearly average equal to the SIL 2 limit of 0.01 and solve: 43.8 hours a year. That is 0.5% of the year, under two days, which is a single routine maintenance job.

What a compensating measure buys

The honest response to a bypass is a compensating measure: while the function is off, something else carries the protection. Suppose an operator watching the pressure covers it with a probability of failure of 0.1 instead of 1. Then 72 hours of bypass gives 0.0058, still SIL 2. The measure is worth far more than the equivalent time as a nuisance.

A bypass with no compensating measure, no authorisation and no time limit is the failure. A bypass with all three is a managed state.

The other quiet killer: change

A function is verified for one set of inputs: the devices, the failure rates, the test interval, the architecture. Replace a valve with a different model, lengthen the test interval, change the process so demands become frequent, and the verified number belongs to a different function. Management of change is the discipline of asking, before any modification, which assumptions in the SIL verification it touches, and recalculating before approving it.

Skipping the proof test (article two) is itself a change, one that rarely goes through that gate.

What this simple model leaves out

It treats a bypass as a complete loss of the function, assumes the bypass hours add up evenly, and prices the compensating measure with a single guessed probability. The data is illustrative. This is for understanding, not for certifying a design.

If you added up every hour your safety functions were bypassed last year, would you know the total?