Here is how to make a plant so safe that nobody can run it.
Choose every voting arrangement to maximise safety and ignore false trips. The plant stops for no reason, production is lost, and people begin to ask who is allowed to switch the safety function off.
Now run that backwards. A safety function that trips too often is not safe. It trains people to defeat it.
This is part of the series that starts with How a SIL calculation works, and it follows 1oo2 vs 2oo3 voting. The data is illustrative, not from a client, and the cost per trip is an assumption.
The narrated walkthrough, about two minutes, with a synthetic voice.
The safe side of the failure rates
So far we counted only dangerous failures. A device can also fail safe, tripping the plant when nothing is wrong. For this article we assume illustrative safe failure rates: 3.0×10⁻⁶ per hour for the transmitter, 5.0×10⁻⁶ for the logic solver and 1.5×10⁻⁶ for the valve, 9.5×10⁻⁶ per hour in all. Every one of them is a spurious trip.
Over a year (8,760 hours) that is 0.0832 trips, about one every 12.0 years. If each trip costs R250,000 in lost production and restart, an assumption, the expected cost is R20,805 per year.
What the voting choice does to that bill
| Sensor arrangement | False trips per year | Years between false trips | Cost per year | Function PFDavg |
|---|---|---|---|---|
| 1oo1, as worked | 0.0832 | 12.0 | R20,805 | 0.0050 |
| 1oo2 | 0.1095 | 9.1 | R27,375 | 0.0041 |
| 2oo3 | 0.0570 | 17.6 | R14,238 | 0.0041 |
The 1oo2 pair makes the function safer and costs R6,570 more a year in false trips. The 2oo3 set makes the function equally safe and cuts the bill by R6,567 a year, a saving to set against the cost of the third sensor. Voting is a trade, and 2oo3 is the one choice here that does not ask you to give something up.
The false trip that hurts most
A nuisance trip has a visible cost, in lost production. The other cost is invisible: the function that trips often gets a bypass, a raised setpoint, or a “temporary” override. A bypass puts the function out of service, and what that does to the SIL is the subject of the next article. The most dangerous false trip is the one that ends with someone switching the guardian off.
What this simple model leaves out
Real spurious trip rates are driven by many causes outside the safety function, including power dips, process upsets and operator actions. The safe failure rates and the cost per trip are assumptions for illustration, not data from a plant.
When your safety function trips for no reason, what is the first thing someone is tempted to do to it?