Here is how to build a safety function with an excellent PFDavg that is too slow to matter.
Get the failure probability right. Pass the architecture check. Certify every device. Then let the valve take a little longer to close each year as its seals age. The function is on paper still SIL 2. In the plant it closes after the damage is done.
Now run that backwards. A safety function has two jobs: work when needed, and work in time. The SIL number only measures the first.
This is the last article in the series that starts with How a SIL calculation works. The data is illustrative, not from a client.
The narrated walkthrough, about two minutes, with a synthetic voice.
The valve is where the numbers pile up
In the worked example the valve ESDV-101 carries 53.9% of the function’s PFDavg. Everything this series found about hidden failures bites hardest here:
- It is the device whose diagnostic credit is hardest to earn.
- It is the device whose proof test misses the most.
- It is the device that gains most from a partial stroke test.
- It is the part of the architecture check with the weakest SFF, 89.1% as worked and 27.3% without diagnostics.
Time is a separate requirement
The process safety time is how long the process can run from the moment a dangerous condition starts until the hazard happens. The function must detect, decide and act inside it. Suppose, as an illustration, it is 10 seconds.
| Step | Time |
|---|---|
| Sensor response (PT-101) | 1.0 s |
| Logic solver scan and decision | 0.5 s |
| Valve closing (ESDV-101) | 8.0 s |
| Total | 9.5 s |
| Margin against 10 s | 0.5 s |
The margin is only 5%. The valve may take at most 8.5 s to close before the function is late. That is a slowing of 6.25%, a fraction of what a worn seal, a stiff stem or a weak spring can cost over a few years.
A function that is late is not a function with a slightly higher PFD. It is a function that, on that demand, does not protect.
What to do about it
- Measure the stroke time at every proof test and record it, not just pass or fail.
- Trend it. A valve that closes in 8.0 s, then 8.2 s, then 8.4 s is telling you when it will fail the requirement.
- Set an alarm limit on stroke time below the process safety time minus the other steps, so the warning comes before the failure.
- Treat a slow valve as a failure of the safety function, not as a note in the test report.
What this simple model leaves out
The response times are assumptions, and real functions have more steps (solenoids, relays, actuators) and variable demands. The data is illustrative. This is for understanding, not for certifying a design.
When did you last record how long your safety valve takes to close, and is the number getting bigger?