Here is how to make a safety function look safer than it is, without changing a single device.
Credit it with diagnostics it does not have.
Nothing physical moves. The sensor, the logic solver and the valve stay exactly where they are. One column in a spreadsheet changes, and a function that was SIL 1 becomes SIL 2 on paper. Now run that backwards, because it shows what the number is really made of.
This is the third article in a series that takes the worked example from How a SIL calculation works apart, one assumption at a time. The numbers are the same illustrative ones, and they are not from a client.
The narrated walkthrough, about two minutes, with a synthetic voice.
Four ways a device can fail
Every dangerous failure rate in that example was split in two, and that split is the whole subject here.
- Dangerous detected (λDD): the device fails, and its own diagnostics notice. The plant is alerted and the repair clock starts, so this failure is short-lived.
- Dangerous undetected (λDU): the device fails, and nothing notices. It sits there, silent, until a proof test or a real demand finds it.
Diagnostic coverage is the share of dangerous failures that fall in the first group:
DC = λDD ÷ (λDD + λDU)
For our three devices:
| Device | λDU | λDD | Diagnostic coverage |
|---|---|---|---|
| PT-101, sensor | 2.1e-07 | 1.2e-06 | 85.1% |
| Logic solver | 3.0e-07 | 2.3e-06 | 88.5% |
| ESDV-101, valve | 6.0e-07 | 3.4e-06 | 85.0% |
Taken together, 86.1% of this function’s dangerous failures are assumed to be caught by diagnostics.
Remember the shortcut warned against in the first article, λDU ÷ (λDU + λDD)? It is simply 1 minus the diagnostic coverage: 14.9%, 11.5% and 15.0% here. It is a ratio, not a probability, but now you can see exactly what it is a ratio of.
Why the split matters so much
The two groups are charged very differently in the calculation. A silent failure is charged for half a test interval, 4,380 hours. A detected failure is charged only for the repair time, 24 hours. That is 182.5 times less, for the same failure rate.
So moving failure rate from the silent group to the detected group is the cheapest improvement in the whole calculation. It is also the easiest one to claim and the hardest one to earn.
Take the credit away
Start from the worked function: PFDavg = 0.0050274, SIL 2. Then remove the credit one step at a time.
| Case | PFDavg | Result |
|---|---|---|
| As worked (86.1% of dangerous failures detected) | 0.0050 | SIL 2 |
| The valve has no diagnostics at all | 0.0198 | SIL 1 |
| No device has any diagnostics | 0.0351 | SIL 1 |
| The repair takes a week (168 h), not a day | 0.0060 | SIL 2 |
Look at the last row. Make repairs seven times slower and the function is still SIL 2. The repair time barely matters, because detected failures are cheap whichever way you count.
Look at the second row. The valve is the problem. Its silent failures were already the largest single contribution, and without diagnostics every one of its dangerous failures becomes silent. That one change takes the whole function from 0.0050 to 0.0198, a fourfold rise, and out of SIL 2.
Why a valve is where it is hardest
A sensor and a logic solver can check themselves. They compare readings, watch their own signals and run internal tests all the time. A valve sitting open in a pipe cannot tell you that it would stick if it were asked to close. It has to be moved to find out, and moving a shutdown valve means interrupting the process.
That is why diagnostic credit for a valve usually rests on something extra, most often a partial-stroke test, where the valve is moved a little and its response is watched. Whether that is in place, working and actually trusted is a fact about the plant, not about the formula.
The break-even
How much diagnostic coverage does the valve really need? Solving the equation for the valve, with the sensor and logic solver unchanged, the whole function stays inside SIL 2 only if the valve’s diagnostic coverage is at least 56.5%.
The worked example claims 85.0%, so there is headroom. The honest question is not whether that headroom exists on paper. It is whether you can show that at least 56.5% of this valve’s dangerous failures really are detected, and how.
Where the series goes next
The architecture check that this number feeds is in hardware fault tolerance and safe failure fraction. The test side of the same question is in proof test coverage, and voting is in 1oo2 vs 2oo3. The full list starts with How a SIL calculation works.
What this simple model leaves out
- It treats diagnostic coverage as one number per device. Real coverage depends on which failures are possible and which the diagnostics can see, and the claim should come from the manufacturer’s data or a test, not from a hope.
- It does not use the safe failure fraction, the architectural check that also asks how many failures are safe. That is a separate number and a later article.
- It uses the simplified single-channel formula and illustrative data. It is for understanding, not for certifying a design.
Which of the diagnostic credits in your SIL calculations could you actually defend with evidence?