Here is how to fail a SIL 2 verification when the arithmetic says you passed.
Do the calculation well. Get the PFDavg inside the band. Then hand the report to an assessor who asks one more question: what does the architecture allow?
Now run that backwards. A PFDavg inside a band is necessary, not sufficient. The standards add a second test that has nothing to do with time: how many failures does the device survive safely, and how many faults can the arrangement tolerate before it stops working?
This is part of the series that starts with How a SIL calculation works, whose closing section already warned that architectural constraints are a separate check. Here they are. The data is illustrative, not from a client.
The narrated walkthrough, about two minutes, with a synthetic voice.
Two terms
Safe failure fraction (SFF) is the share of all failures that are either safe, or dangerous but caught by diagnostics:
SFF = (λS + λDD) ÷ (λS + λDD + λDU)
Only the dangerous undetected failures count against you. Hardware fault tolerance (HFT) is how many faults the arrangement can absorb and still do its job. A single sensor has HFT 0. A 1oo2 pair has HFT 1. A 2oo3 set also has HFT 1.
The worked numbers
The earlier articles gave dangerous failure rates. For SFF we also need safe failure rates, so we add illustrative ones: 3.0×10⁻⁶, 5.0×10⁻⁶ and 1.5×10⁻⁶ per hour for the transmitter, logic solver and valve.
| Device | SFF as worked | SFF if its diagnostics do not exist |
|---|---|---|
| PT-101, sensor | 95.2% | 68.0% |
| Logic solver | 96.1% | 65.8% |
| ESDV-101, valve | 89.1% | 27.3% |
The right-hand column is the situation from the diagnostic coverage article: take away the credit for diagnostics and every dangerous failure becomes silent. The PFDavg moves, and now the SFF moves too.
How the veto works
IEC 61508-2 sets a maximum SIL for each combination of device type, SFF band and hardware fault tolerance (its route 1H). Complex devices with software, such as a smart transmitter, are Type B. One cell from that table is enough to see the principle: a Type B element with HFT 0 needs an SFF of at least 90% to be used alone in a SIL 2 function.
Our transmitter, as worked, sits at 95.2%, so a single one can be used. Without its diagnostics it falls to 68.0%. The calculation would be unchanged in form, the arithmetic would be worse, and now the architecture also forbids a lone sensor. The fix is a second sensor, which raises HFT to 1.
The other cells depend on device type and the edition of the standard, and IEC 61511 has its own fault tolerance requirements in clause 11.4, so look up the exact table for your case rather than relying on a summary.
A trap in the number itself
SFF rewards safe failures. A device that trips the plant often, for no reason, scores a high SFF. High SFF and high availability are different goals, and the next articles show what false trips cost.
What this simple model leaves out
The safe failure rates are assumptions added for this article, and device type, proven-in-use arguments and the 2H route all change the answer for a real design. This is for understanding, not for certifying anything.
Does your SIL verification report show the architecture check next to the PFD check, or only the arithmetic?