Articles / Safety

SIL 3 plus SIL 3 plus SIL 3 equals SIL 2: why a certified device is not a certified loop

24 November 20263 min read

Here is how to build a SIL 3 function out of nothing but SIL 3 devices, and get SIL 2.

Buy a SIL 3 sensor, a SIL 3 logic solver and a SIL 3 valve. Wire them in a row. The brochures say SIL 3 three times. The loop says something else.

Now run that backwards. A SIL is a band of the chance of failure. A loop fails if any link fails, so the chances add, and the sum is bigger than any one of them.

This is part of the series that starts with How a SIL calculation works. The data is illustrative, not from a client.

The narrated walkthrough, about two minutes, with a synthetic voice.

The arithmetic

Suppose each of three devices sits comfortably inside the SIL 3 band, at a failure probability of 0.0009 (the band runs from 0.0001 to 0.001). In a series loop the probabilities add:

0.0009 + 0.0009 + 0.0009 = 0.0027

That is inside the SIL 2 band (0.001 to 0.01), not SIL 3. Even three devices right at the SIL 3 limit of 0.001 add up to 0.003, which is SIL 2. To keep the whole loop under 0.001, the three devices together must fit inside that figure, about 0.00033 each if they share it equally.

What the worked example shows

In SIF-101 the contributions are not equal. The sensor is 18.9% of the total, the logic solver 27.2% and the valve 53.9%. The loop is as good as its weakest large contributor, and the valve is it. The budget is shared out by what each device really costs, not by the label on the box.

What a device certificate does say

A device certificate is a statement about the device under stated conditions. It usually carries the failure rates, the diagnostic coverage, and a systematic capability (a measure of how well the design process guards against built-in faults), together with a safety manual of conditions: test interval, mission time, configuration, environment.

It does not say what the device’s contribution to your loop is. That depends on how you use it.

When the assumptions walk away

Our transmitter’s contribution is 0.00094860, assuming a 12-month test. Test it every 24 months instead and its own contribution rises to 0.0018684, 1.97 times larger. The whole function moves from 0.0050 to 0.0059. The certificate was never wrong. The assumption it was built on was no longer true in your plant.

What to check

  • The loop total, computed from every device’s failure data, not the highest label.
  • Each device’s certificate conditions against how it is actually used and tested.
  • The architecture check (hardware fault tolerance and SFF) for each subsystem.

What this simple model leaves out

It adds probabilities in a simple series loop and treats the certificate’s contents in general terms. Real certificates and safety manuals differ. The data is illustrative, and this is for understanding, not for certifying a design.

Which of the SIL claims in your plant belong to a device, and which have been proved for the loop?